Test
Menu Item Display Default Range Setting
Heater output
Test HeatOut
Off
On
High limit relay
Test HiLimOut
Off
On
Relay 1 output
Test Rly1 Out
Off
On
Relay 2 output
Test Rly2 Out
Off
On
Relay 3 output
Test Rly3 Out
Off
On
Relay 4 output
Test Rly4 Out
Off
On
High Limit Sensor
Test HL Temp
(sensor reading)
Zone Cal
Menu Item Display Default Range Setting
Zone 1 actual
Zone Cal Zone1Act
38°C
-73°C to 760°C (-100°F to
1400°F)
Zone1 displayed
Zone Cal Zone1Dis
38°C
-73°C to 760°C (-100°F to
1400°F)
Zone 2 actual
Zone Cal Zone2Act
260°C
-73°C to 760°C (-100°F to
1400°F)
Zone2 displayed
Zone Cal Zone2Dis
260°C
-73°C to 760°C (-100°F to
1400°F)
Factory calibration*
Zone Cal FactCal
Ready
Ready or Done (push- key)
*only use when no calibration instrument is available
Sensor Cal
Menu Item Display Default Range Setting
Control Sensor Cal
Ctrl Sens 0F
Ctrl Sens 1000F
Ctrl Sens Done
-100°F
1400°F
Done
-100 to 1400°F
-100 to 1400°F
(read only)
HiLim Sensor Cal
HL Sens 0F
HL Sens 1000F
HL Sens Done
-100°F
1400°F
Done
-100 to 1400°F
-100 to 1400°F
(read only)
Retransmit Cal
RetCalLo XXXX *
RetCalHi XXXX *
0
4096
0 to 4096**
0 to 4096***
* note that the actual RetCalLo and RetCalHi values displayed are of no importance.
** press keys until retransmission output = 1VDC
*** press keys until retransmission output = 5VDC