21
Option Slot 3 - SSR Driver Output Module
If option slot 3 is fitted with an
SSR
driver output module, make connections as illustrated. The solid-
state relay driver is a 0-10V DC signal; load impedance must be no less than 500 ohms. SSR driver
outputs are not isolated from the signal input or other SSR driver outputs.
Figure 24. Option Slot 3 - SSR Driver Module Connections
Option Slot 3 - Linear Voltage or mADC Output module
If option slot 3 is fitted with a DC linear output module, make connections as illustrated.
Figure 25. Option Slot 3 - Linear Voltage & mADC Module Connections
Option Slot 3 - Transmitter Power Supply Module
If option slot 3 is fitted with a transmitter power supply module, make connections as illustrated. The
output is an unregulated 24V DC, 22mA supply.
Figure 26. Option Slot 3 - Transmitter Power Supply Module Connections
WARNING:
THIS MODULE MUST NOT BE FITTED INTO OPTION SLOT 2.
10
11
_
12
+
10
11
_
12
+
10
11
_
12
+