ADDRESS LIST Modbus Programming Manual
38 Version 2
Copyright © 2012 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Creating A Profile Header - Request (to instrument)
16 characters of the profile name, e.g. :
A = 65dec / 0x41, B = 66dec / 0x42 etc
a = 97dec / 0x61, b = 98dec / 0x62 etc
Note: Only valid characters from the
instruments supported character set
should be used
The space character (32dec / 0x20hex) is
used to fill any unused characters at the end
of the name.
Characters 9 to 16 are not supported and
should be written to 32dec / 0x20hex
Profile Name Character 10
Profile Name Character 11
Profile Name Character 12
Profile Name Character 13
Profile Name Character 14
Profile Name Character 15
Profile Name Character 16
Profile Start Signal High Byte
0 = No delay, 1 = After delay, 2 = At
Time/day
Profile Start Signal Low Byte
Profile Start Time (Byte 4 - High)
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Profile Start Time (Byte 1 - Low)
Profile Start Day High Byte
1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday,
10 = Saturday And Sunday, 11= All Week
Profile Start Day Low Byte
Profile Starting Setpoint High
1 = Current Process Variable Value
Profile Starting Setpoint Low
Profile Recovery High Byte
0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint,
4 = Continue profile from where it was when
power failed
Profile Recovery Low Byte
Profile Recovery Time (Byte 4 - high)
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Profile Recovery Time (Byte 1 - Low)
Profile Abort action High Byte
0 = Control to off
1 = Maintain last profile setpoint
Profile Abort Action Low Byte
1 to 9999 or 10,000 for “Infinite”
The instrument replies to this message with an Edit Response Message Section 2.9.5.9.